4 Core 50 sq mm 0.6/1kV Stranded Aluminium XLPE Cable, Steel Tape Armed | Alfanar
(167 Product Views)
Four core stranded aluminium armored cable (AL/XLPE/STA/PVC), armored with double layers of galvanized steel tapes (STA), to give it mechanical strength to protect it from external pressures that fall on the cable, conductor Size 50 mm2 ,phase core color (red, yellow, blue, black), from Alfanar Company.
Product description
Four core stranded aluminium armored cable (AL/XLPE/STA/PVC), Produced by Alfanar Company, Armored with double layers of galvanized steel tapes (STA) to give it mechanical strength to protect it from external pressures that fall on the cable. Insulated with XLPE (cross-linked polyethylene), which offers an exceptional combination of properties that make it the ideal choice for a wide range of power and energy transmission applications due to its excellent electrical, thermal, and mechanical properties, where it is characterized by its ability to withstand high temperatures up to 90°C for extended periods without compromising performance. It also offers excellent resistance to moisture, corrosion, and chemicals, ensuring long-term safety of use. Additionally, sheathed in PVC (polyvinyl chloride) material, which provides extra protection for the cable against shocks, abrasion, corrosion, and prevents harmful UV rays from damaging the cable. This makes it suitable for both indoor and outdoor applications where there is a risk of mechanical damage. Available in different shapes, sizes and conductor ratings to meet diverse application requirements.
- Conductor Type: Aluminium
- Insulation Material: XLPE (Cross-Linked Polyethylene)
- Armouring: Double Layers of Galvanized Steel Tapes (STA)
- Outer Jacket: PVC
- Voltage: 600/1000 volts
- Conductor Shape: Sector Shaped (sm)
- Number of Cores: 4
- Conductor Size (Cross-Sectional Area): 50 mm2
- Max DC Conductor Resistance at 20°C: 0.6410 ohm/km
- Max AC Conductor Resistance at 90°C: 0.8224 ohm/km
- Current Rating Laid in Ground: 129 Ampere
- Current Rating Laid in Ducts: 99 Ampere
- Current Rating Laid in Free Air: 132 Ampere
- Approx Overall Diameter: 29.5 mm
- Weight: 1180 kg/km
- Phase Core Colors: (Red, Yellow, Blue, Black)
- Standard: IEC 60502-1